Split Airconditioner : Circuit Breaker (MCB Trip) activates during operation.
Last update date : 2017.01.03
[Cause]
A low-rating circuit breaker (MCB) is used.
[Solution]
If Circuit Breaker (MCB Trip) activates during operations, please check the followings.
Step 1.
● Check whether the 16 Amp good Quality Top plug is used or not.
● Check whether Switch is ON and the Power is supplied.
Step 2.
● Check if there is a loose connection between plug and socket. It may increase the unit of electric current (amp).
Step 3.
● Check proper ear thing with the related voltage.
Important check list
● Always use a properly rated Breaker (MCB) according to product capacity.
Capacity |
Current (AMP) |
Breaker size |
0.75 ton |
5~6Amp |
16 Amp |
1.0 ton |
6~7Amp |
20 Amp |
1.5 ton |
8~10Amp |
32Amp |
2 ton |
15~16Amp |
40Amp |
● Under size breaker may cause Tripping.
● Refrigerant over-charge may also cause Tripping.
● If there is any Phase leakage, it may also cause Tripping.
[Important Reminders]
● Depending on national regulations and your specific installation, you may need to install a circuit breaker.
● For further information on electrical requirements, contact a professional electrician.
● This device must be installed according to the national rules.