Split Airconditioner : Circuit Breaker (MCB Trip) activates during operation.

Last update date : 2017.01.03

[Cause]

A low-rating circuit breaker (MCB) is used.

 

[Solution]

If Circuit Breaker (MCB Trip) activates during operations, please check the followings.

 

Step 1.

                          Check whether Switch is ON and the Power is supplied.

● Check whether the 16 Amp good Quality Top plug is used or not.

● Check whether Switch is ON and the Power is supplied.

 

Step 2.

                                            Check if there is a loose connection between plug and socket.

● Check if there is a loose connection between plug and socket. It may increase the unit of electric current (amp).

                 Plug and socket

 

Step 3.

● Check proper ear thing with the related voltage.

                Check proper earthing with the related voltage.

Important check list

● Always use a properly rated Breaker (MCB) according to product capacity.

Capacity  

Current (AMP)

Breaker size

0.75 ton  

5~6Amp  

16 Amp

1.0 ton

6~7Amp

20 Amp

1.5 ton

8~10Amp

32Amp

2 ton

15~16Amp

40Amp

 

Under size breaker may cause Tripping.

Refrigerant over-charge may also cause Tripping.

If there is any Phase leakage, it may also cause Tripping.

 

[Important Reminders]

● Depending on national regulations and your specific installation, you may need to install a circuit breaker.

● For further information on electrical requirements, contact a professional electrician.

● This device must be installed according to the national rules.                             